莫帝斯燃烧技术(中国)有限公司
高级会员第2年 参观人数:90939
  • 参考报价:电议
    型号:
    产地:江苏
    在线咨询
  • 详细介绍:


    仪器简介:

    The Radiant Panel Flame Spread Tester is an equipment using gas ignited Radiant heat panel to test the surface combustibility of Building product (ASTM E 162) and cellular plastics (ASTM E 365), Radiant Panel Index(Is) is measured by the flame radio waves, Critical Heat Flux,(CHF) and Heat Release Rate(kW/m2).

    技术参数:

    • ASTM E 162: Standard Test Method for surface Flammability of materials Using a

    Radiant Heat Energy Source

    • ASTM D 3675: Standard Test Method for surface Flammability of Materials using

    A Radiant Heat Energy Source

    主要特点:

    • Reflection panel is composed of a cast iron frame with vertically applied

    porosity fire resistant material with a 305X457mm size exposed reflection surface

    and is designed to function at 815 ℃.

    • The Calibration burner should have 1.8mm holes in 16mm intervals, and should

    be manufactured along the middle line.

    • An exhaustion device with a 0.5 m/s airflow exhaustion rate is installed.

    • In order to control the surface heat of the reflection panel, a 180℃ ~ 230℃

    (Black body temperature) range will be given, and a ±5℃ accuracy, fit to observe

    a surface of 250mm radius at 2 m distance.

    • Base Structure Units

    - Frame dimension : 1850 (H) X 700 (D) X 1250 (L)

    - Electrical Power : 220 V AC, 60 Hz, 12 A

    - Sliding platform for loading of the test specimen

    - Radiant Panel (90°, Porous cement)

    - 19" Touch Screen Panel Computer for control & Acquisition Data

    • Radiant Panel with Air and Gas Supply

    - Radiant Panel Size : 300 by 460 (mm)

    - Fine Brick : Max Temp : 815℃ (1500℉)

    - Pilot Burner : Acetylene(0.5 l/min, 150 mbar)

    - Calibration Burner : Methane gas(95% purity, 20 l/min, 150 mbar)

    - Propane Burner : Pressure(1.0 l/s, 20 mbar)

    - Compressed Air Burner : 50 l/s, 700 Pa of water

    - Digital anemometer : 0.5 m/s

    • Analysis & Controls

    - Heat Flux Meter : Schmidt - Bolter type, Range : 0 ~ 100 ± 10 ?/㎡

    - Portable water cooling system for heat flux meter

    - Pyrometer for measuring radiant panel temperature

    - DAQ (Data Acquisition) System(GPIB/USB Interface)

    • Application Software

    - ASTM E 162 Operation & DAQ Program

    - Test Calibration Program